Previous Page | Next Page Contents Glossary Index Preparing the Physical Environment > Environmental Impact >

Heat/Power

The heat dissipation values in the following table apply equally to Infoprint 4000 Models IS1 and IS2.

Table 17. Heat dissipation and power for Models IS1 and IS2
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
42 lb 20 lb 28 lb
kVA 3.5 3.4 12.0 10.6 12.4
kW 3.0 2.8 11.3 10.4 12.2
kBTU/Hr 10.2 9.6 40.32 35.6 41.6
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.
  2. Measured at 28 lb.

The heat dissipation values in the following table apply equally to Infoprint 4000 Models ID1 or ID2.

Table 18. Heat dissipation and power for Models ID1/ID2
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
42 lb 20 lb 42 lb
kVA 3.5 3.4 11.5 8.8 11.9
kW 3.0 2.8 11.3 8.7 11.7
kBTU/Hr 10.2 9.6 38.6 29.7 40.1
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.

The heat dissipation values in the following table apply equally to Infoprint 4000 Models ID3/4 and ID5/6.

Table 19. Heat dissipation and power for Infoprint 4000 Models ID3/ID4, ID5/ID6.
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
42 lb 20 lb
kVA 3.6 3.5 N/A 10.8
kW 3.1 2.9 N/A 10.4
kBTU/Hr 10.2 9.6 N/A 36.9
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.

The heat dissipation values in the following table apply equally to Infoprint 4000 Models IR1 and IR2.

Table 20. Heat dissipation and power for Models IR1/IR2
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
42 lb 20 lb
kVA 3.6 3.5 N/A 7.5
kW 3.1 2.9 N/A 7.3
kBTU/Hr 10.6 9.9 N/A 24.5
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.

The heat dissipation values in the following table apply equally to Infoprint 4000 Models IR3 and IR4.

Table 21. Heat dissipation and power for Models IR3/IR4
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
42 lb 20 lb
kVA 3.5 3.4 N/A 9.0
kW 3.0 2.8 N/A 8.7
kBTU/Hr 10.2 9.6 N/A 30.7
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.

The heat dissipation values in the following table apply equally to Infoprint 4100 models HS1, PS1, PD1/2, and HD1/2.

Table 22. Heat dissipation and power for Infoprint 4100 models HS1, PS1, PD1/2, HD1/2.
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
20 lb 20 lb
kVA 3.6 3.6 9.6 9.6
kW 3.1 3.1 9.0 9.0
kBTU/Hr 10.2 9.6 30.7 30.7
Notes:
  1. 50 Hz printing may be expected to operate within 10% of the 60 Hz values.

The heat dissipation values in the following table apply equally to Infoprint 4100 models HS2, HD3/4.

Table 23. Heat dissipation and power for Infoprint 4100 models HS2, HD3/4.
  Idle Ready Mode Printing
50 Hz 60 Hz 50 Hz 60 Hz
20 lb 20 lb
kVA 3.0 3.0 12.5 12
kW 2.0 2.0 12 12
kBTU/Hr 6.8 6.8 41 41